ASHRAE Guideline 43 gives hospitals a nine-step ventilation rulebook

ASHRAE Guideline 43, adopted in June 2025, asks hospitals to write a Ventilation Management Program governing how HVAC systems run day to day. Its Appendix F lays out nine steps. With the 2027 NFPA 99 recognizing these programs, hospital ventilation decisions are moving from maintenance judgment into committee-approved documents that facilities teams present at survey time.

This story was produced through MarketScale. See how Building Management teams put it to work with Customer Stories & Case Studies.

By MarketScale Newsroom · Ashrae Guideline 43Ashrae Standard 170Ventilation Management ProgramNfpa 99
Share
ASHRAE Guideline 43 gives hospitals a nine-step ventilation rulebook

Key takeaways

01

Standard 170 sets what an operating room must be able to do; a Ventilation Management Program records who decided what it actually does after hours, and on what evidence.

02

The 2027 NFPA 99 recognizes HVAC Ventilation Management Programs in Chapter 9, and a September 2026 Standard 170 addendum requires a risk assessment before operating room ventilation is adjusted.

03

For hospitals whose inspectors still enforce older editions, the first useful step is confirming in writing which Standard 170 edition applies, since every later rule in the program depends on it.

Free workspace

Turn your Building Management expertise into content.

Record interviews, organize footage, and write with AI on a free trial of the MarketScale platform for qualifying companies. No demo required, no credit card.

Try it Free

Hospital air handlers are designed against a published national standard. Until June 2025, there was no shared playbook for running them. That month ASHRAE and the American Society for Health Care Engineering (ASHE) adopted Guideline 43, which asks hospitals to produce a Ventilation Management Program, or VMP: a written, risk-assessed set of rules for operating HVAC systems day to day while staying clinically compliant.

Buildings, in a Nov. 11 piece by Valerie Dennis Craven, laid out what facility managers should do with it, drawing on Dino Coliano, a consultant for Setra, founder of AVANZARE Services and a Senior ASHE member. His read on the starting point: before Guideline 43, no two hospital ventilation programs he had seen across the country looked alike, because every health system built its own from scratch.

Standard 170 is the design standard: That's how I built my building. There's nothing in Standard 170 that tells me how to operate it day-to-day., Dino Coliano, consultant for Setra and founder of AVANZARE Services, to Buildings

Only a small number of systems have created or adopted a VMP so far, and several of them helped write the guideline and tested it in their own hospitals. Coliano says he hears from plenty of other facility managers who know the guideline exists but are unsure how it supports their role. His answer is that it gives them ground rules and a place to start.

The payoff is concrete. When a Joint Commission surveyor or another authority questions an operating setting, a facilities director with a VMP can hand over a documented policy approved by a multidisciplinary committee, instead of defending a call one maintenance department made alone. Two other documents now point the same way, which makes this a planning item for hospital facilities leaders rather than a reading assignment.

Where the design standard runs out

ANSI/ASHRAE/ASHE Standard 170 works room by room. In a Nov. 5 guide, mechanical contractor Blume Mechanical describes the standard's design tables: 7-1 for inpatient spaces, 8-1 for specialized outpatient and 9-1 for residential care. Since 2021 they have covered more than 80 room types. Each row specifies filtration, pressure relationships and air change rates, and lists temperature and humidity next to them.

The guide cites ASHRAE's own framing of the standard: a minimum set of design requirements meant for code-enforcing agencies to adopt. The operating room row shows how specific the design side gets. ASHRAE reproduced it in Addendum y, approved Sept. 22, 2026.

The operating room, as Standard 170-2025 designs it

20 ach
Minimum total air changes per hour; a room balanced to exactly this has no margin for loaded filters
4 ach
Minimum outdoor air changes per hour, the dilution recirculation can't provide
MERV-16
Minimum filter efficiency for the room's supply
20 to 60% RH
Design humidity range; the floor a hospital actually runs is an operating decision

ASHRAE Addendum y to Standard 170-2025, via Blume Mechanical

Those are design minimums, and Blume Mechanical makes the point that they are not targets. Because air changes are calculated on room volume, the guide adds, ceiling height changes the airflow a room needs. Per the Buildings account, Standard 170 stops at how to run systems dynamically or respond when conditions change.

Since 2021, each row has also stated whether airflow to an unoccupied space can be reduced, as long as its pressure relationship is maintained. The operating room row allows it. ASHE notes that the 2025 edition clarifies turndown requirements for outpatient spaces. Permission is a design fact. Operating facts are a separate set of questions: which rooms turn down, in which hours, who signs off, and what happens when pressure drifts. Until Guideline 43, those questions had no common home.

Pressure is where that gap shows up fastest. Blume's guide notes that for airborne infection isolation and protective environment rooms, the standard calls for a permanently installed monitoring device and a differential of at least 0.01 in. w.c. (2.5 Pa). The monitor will flag a drift whether or not anyone has agreed on the next step. A VMP's response plan exists to settle that decision ahead of time.

Humidity shows the same gap. The 20 percent floor in the operating room row dates to a 2010 addendum. A 2013 CMS waiver let hospitals run anesthetizing locations at 20 percent relative humidity instead of an older 35 percent NFPA figure, provided they documented the choice and kept monitoring; CMS later noted that some surgical supplies are labeled for a 30 percent minimum. The floor a hospital actually holds therefore depends on what is in its supply rooms.

Neither end of the range is free. AORN guidance cited in the Blume guide holds that too little humidity raises static and airborne, bacteria-carrying dust, while too much leaves supplies damp and gives mold a foothold. Temperature brings in a clinical voice as well: the operating room row carries a 68 to 75°F design range, and surgeons routinely ask for rooms cooler than 68°F, per the same guide. These are exactly the kinds of decisions a VMP's committee could settle once and write down.

Standard 170 sets what an operating room must be able to do; a Ventilation Management Program records who decided what it actually does after hours, and on what evidence.

Appendix F, step by step

Coliano's advice is to build the program by following Appendix F of Guideline 43, which sets out the process in nine steps:

  1. Form a committee
  2. Determine the code reference
  3. Develop a source of truth
  4. Weigh risk and performance metrics
  5. Create a response plan
  6. Provide education
  7. Develop the policy
  8. Gain approval
  9. Maintain the plan

The order does real work. The committee comes before any policy, and it is meant to span facilities, infection prevention, nursing, clinical leadership and executive management. Coliano's case for that breadth is that a formal VMP "ensures we have multi-disciplinary input in how we operate and maintain our spaces, equipment, and HVAC systems."

Step two, the code reference, is less trivial than it sounds. ASHE warns that local and national authorities having jurisdiction have adopted and enforce different editions of Standard 170, and tells organizations to confirm with their own authority which one applies. Its catalog still lists the 2008, 2017, 2021 and 2025 editions, which suggests how far apart two hospitals' reference points could sit. Every number in the source of truth hangs on that answer.

The source of truth itself can take whatever form a hospital chooses, whether a binder, a maintenance-system workflow or rules in the building automation system; the reporting does not prescribe one. What the early adopters shared, in Coliano's telling, was less about format. Each had an internal change agent who put ventilation on the executive agenda, a facilities team that brought the clinical side in to review and approve operating parameters, written policies with pre-written responses for excursions, and the expectation that standards would eventually require all this anyway.

The pre-written excursion responses carry most of the time savings. A pressure loss or humidity spike in a sensitive room is not the moment to convene infection prevention and nursing for the first time. Coliano's working rule for the finished plan is to educate staff to it, operate and maintain to it, and monitor against it.

The codes are catching up

Buildings reports that Chapter 9 of the 2027 edition of NFPA 99, the Health Care Facilities Code, recognizes HVAC Ventilation Management Programs. Standard 170 itself is also moving toward operations. According to Blume Mechanical's guide, a September 2026 addendum means operating room ventilation cannot be adjusted until a risk assessment has been done. ASHRAE and ASHE publish a new edition of the standard about every four years and issue addenda between editions.

Guidelines and consensus standards are voluntary until adopted. Healthcare Facility Hub notes the FGI documents, which pull Standard 170's ventilation numbers into hospital design, become mandatory when a state or local jurisdiction adopts them (43 states have) or an accreditor or payer requires them.

The design side is tightening at the same time. Standard 170 has been part of the Facility Guidelines Institute's hospital documents since 2010. With the 2022 edition, the ventilation requirements were moved wholly into the standard, according to Blume's guide, which cites Health Facilities Management. FGI's 2026 documents came out in September 2026 under the name FGI Codes for Planning and Design. They contain only minimum requirements, and the explanatory material now sits in subscription Handbooks. Blume points to Healthcare Design and Medical Construction & Design for that change. Healthcare Facility Hub argues the split makes the Codes more enforceable.

ASHE says Standard 170-2025 added space types to line up with FGI 2026. Its list of other 2025 changes includes a reorganized Section 10 on ventilation during construction, updated cooling and heating reserve capacity and on-site fuel requirements, and total outdoor air calculated at the system level for systems serving both Standard 170 and Standard 62.1 spaces. Several of those describe conditions a facilities team lives with long after handover, which is where a VMP's source of truth would need to track them.

Healthcare Facility Hub also points out that the CMS Conditions of Participation make the physical environment a federal requirement, which is why design decisions resurface at survey time. That federal layer is in motion as well. Health Facilities Management reported in mid-November that CMS has proposed updates to the Conditions of Participation code set, under which Medicare- and Medicaid-deemed organizations could soon operate under a new set of physical environment requirements.

Taken together, these indicate that operational ventilation choices are becoming documented, reviewable items in the same way design choices already are. An operating room turndown schedule or an adjusted humidity floor is increasingly something a hospital would be expected to justify on paper.

Where waiting is still defensible

The strongest case against rushing is enforcement. Guideline 43 is a guideline, and recognition in NFPA 99's 2027 edition takes effect for a given hospital only when its authority adopts that edition. Coliano himself is asking associations to train inspectors so they recognize Guideline 43 programs in the field, a sign that recognition is still uneven. For a facility whose authority enforces an older edition of Standard 170, a VMP today is a way to defend settings, not a box a surveyor will tick.

Even then, the opening steps cost little beyond staff time: a committee, a written answer on which code edition applies, and a single agreed list of operating parameters. The reference document is not a budget item either; ASHE lists Standard 170-2025 at $105 for members and $140 for non-members.

Before the first committee meeting, ask the facility's authority having jurisdiction, in writing, which Standard 170 and NFPA 99 editions it enforces. Then list every room where the building automation system currently turns ventilation down when unoccupied, and who approved each one.

The signal to watch is adoption of the 2027 NFPA 99 by state and local authorities, and the first surveys in which inspectors ask to see a Ventilation Management Program rather than simply accepting one when offered. The guidance itself is still drawing input: a Health Facilities Management roundup dated Nov. 6 lists a guideline on healthcare ventilation operations among ASHRAE documents open for public comment, alongside a standard on controlling infectious aerosols. Hospitals that already have the committee and the source of truth in place will be updating a document when that happens, not starting one.

Featured companies

Your experts belong here

Every story in MarketScale Building Management starts with a company putting its facilities engineers, energy managers, and service technicians on the record. Buyers are already reading this topic. The only question is whose experts they find.

Owners and facilities teams pick on trust, and your engineers turn that trust into inbound conversations.

Book DemoSee how it works15 minutes, straight to a calendar.

About the author

MarketScale Newsroom
MarketScale NewsroomEditorial Team, MarketScale

The MarketScale Newsroom reports on the companies, technologies, and trends shaping 16 B2B industries. It turns primary sources and expert commentary into clear, useful coverage for the people doing the work.

B2B Weekly

The week in Building Management, and sixteen other industries, every Monday.

Ten stories, one-line takes, five minutes. Free.

Building Management: are you visible to AI?

Before they reach out, Building Management buyers ask AI engines which vendors to trust. Explore how your experts, customers, and partners can become useful content for buyers and AI search.

Free Trial

You just read one Building Management expert. Your company is full of them.

This article was produced through MarketScale. The same platform turns your facilities engineers, energy managers, and service technicians into the articles, video, and social content Building Management buyers are searching for. Start a free trial and see it with your own people. For qualifying companies, no credit card, no demo required.

NPS +73 · 1,000+ creators · 38+ countries

What your free trial includes

Hands-on access to the MarketScale platform
Media requests to your crowd, remote recording, AI writing tools
No demo required. No credit card.
For qualifying companies. Company confirmation required.

More Building Management Insights

Ken Sinclair's building autonomy roadmap starts with the sensor labels

Ken Sinclair's building autonomy roadmap starts with the sensor labels

Ken Sinclair's five-step roadmap for autonomous buildings keeps existing HVAC hardware and starts by tagging every sensor point in an open ontology. His checklist starts by mapping points into one semantic graph and ends with a one-subsystem pilot where a person approves setpoint changes.

  • 01Sinclair’s step one for autonomy is to map and tag existing automation points so the data is usable. Siemens says its AI-Assisted Data Onboarding automates tagging and structuring for existing buildings.
  • 02Commissioning and fault-detection programs can achieve about 20% savings in some cases, according to a sponsored Facility Executive piece on campuses.

Nov 17, 2026

JLL survey: 75% say FM procurement hasn’t kept up

JLL survey: 75% say FM procurement hasn’t kept up

According to JLL, 87% of occupiers agree FM outsourcing will shift from labor-based to outcome-based pricing by 2030. In the same survey, 75% say procurement has not kept pace with their FM ambitions, and 71% split FM decisions on budget, delivery model and provider selection across two or three functions.

  • 01Nearly nine in ten occupiers expect to pay facilities providers for results by 2030, yet 71% still split the buying decision across two or three functions that each define success differently.
  • 02Strategic FM isn’t necessarily leaner: among JLL’s “strategic operators,” 64% plan bigger FM budgets and 58% plan more headcount even as AI and robotics scale.
  • 03A key question before drafting an outcome-based FM contract: who has the authority to align budget, delivery model and provider selection around one agreed scorecard and baseline?

Nov 16, 2026

Bilt's new AI neighborhood platform is headed to 40,000 American Landmark apartments

Bilt's new AI neighborhood platform is headed to 40,000 American Landmark apartments

American Landmark Apartments is putting 40,000 homes on Bilt Neighborhood OS, an AI agent and local-rewards layer that sits on top of existing property systems. Bilt says agents can coordinate tasks and enable neighborhood benefits. Operators should evaluate apartment-specific agent results and clarify who funds each perk.

  • 01Bilt's 91% unassisted-action rate spans every business type on its platform; the benchmark apartment operators need is the rate for leases, work orders and amenity approvals alone.
  • 02Neighborhood OS runs above the property management system, and the loyalty relationship lives in the resident's Bilt account, which follows that person from landlord to landlord.
  • 03The retention case rests on stated preference so far: 77% of surveyed renters say housing-payment rewards would make them likelier to stay. A deployed portfolio such as American Landmark's 40,000 homes is where observed renewals can be measured.

Nov 16, 2026

Explore More Building Management Insights

Read more expert perspectives from across Building Management.

Browse Building Management Hub

About the Expert

MarketScale Newsroom
MarketScale Newsroom

Editorial Team

MarketScale

The MarketScale Newsroom reports on the companies, technologies, and trends shaping 16 B2B industries. It turns primary sources and expert commentary into clear, useful coverage for the people doing the work.

For B2B teams

Your experts could be publishing here

Stories like this one run on content MarketScale captures from real practitioners. See how your team's expertise becomes coverage in Building Management and beyond.

Book a Demo

Or call us. No forms required. We pick up. 214-945-2512