Why this rooftop HVAC unit can’t just sit on its curb

Anchor Products' Brandon Reynolds inspected a ten-year-old adhered EPDM roof and found HVAC units unattached to their curbs and conduit fastened through the membrane under cracking caulk. Professional Roofing, MicroMetl and ASCE 7-22 frame restraint as an engineered system from unit to curb to structure, while FM Global rates roof assemblies by uplift pressure with a safety factor of two.

This story was produced through MarketScale. See how Building Management teams put it to work with Customer Stories & Case Studies.

By MarketScale Newsroom · · Anchor ProductsRooftop HvacEpdm RoofingWind Uplift
Share

Key takeaways

01

Codes moved past relying on unit weight; many jurisdictions require an engineer’s certification.

02

A hold-down bracket on a standard curb satisfies no wind code by itself; the rated system runs from unit to curb to structure under a professional engineer's stamp.

03

FM Global's uplift ratings carry a safety factor of two, so an FM 1-60 assembly is meant for a 30 psf design load, and the rating number is not a wind speed.

Free workspace

Turn your Building Management expertise into content.

Record interviews, organize footage, and write with AI on a free trial of the MarketScale platform for qualifying companies. No demo required, no credit card.

Try it Free

Brandon Reynolds put one hand on a rooftop HVAC unit and pushed. The unit rocked under one hand. Nothing held it to the curb beneath it, and behind him, past the gutter edge, was a narrow sidewalk and the lot where the building's employees park.

Reynolds, OEM business manager at Anchor Products, was recording a rooftop equipment blind inspection for a MarketScale Studio segment. From the ground he had seen parapets and some equipment and did not know what membrane was up there. On the roof he found adhered EPDM, a rubber sheet glued down to the insulation rather than screwed through it, and a building owner who told him the roof was about ten years old.

The timing comes down to a bead of caulk. Reynolds pointed at the cracks in it and expected them to widen as winter set in.

The question he was asking is also live in the trade. In January 2026 curb maker MicroMetl wrote on its own blog that its sales desk keeps fielding requests for hold-down brackets from buyers who believe the brackets alone satisfy wind code, and in May 2026 rooftop support maker MIRO Industries published its own guide to meeting ASCE 7-22 wind loads without cutting a membrane. Both are manufacturer material, and both exist because facility managers keep asking what Reynolds asked on that roof.

Codes stopped counting unit weight as restraint

Many U.S. jurisdictions require a licensed engineer to certify that curbs and restraints meet the building code, Professional Roofing reported in July 2007. The magazine's explainer by Paul Selman traced how that came about. Before comprehensive codes, crews set rooftop equipment without attaching it to the structure on the theory that a unit's weight would keep it put, and research into natural disasters showed that resisting wind and seismic loads means restraining the unit from leaving its curb and tying the curb to the building.

A curb is the raised frame, flashed into the roof, that a rooftop unit sits on. When wind hits the unit, the connection between unit and curb has to resist tension, shear, moment and uplift, and the curb has to carry those forces into the deck and framing, according to Professional Roofing. Selman described the design as three steps: identify the governing code for the site, calculate the design force from wind or earthquake (both, where it is not obvious which is larger), then specify how the unit attaches to the curb and the curb to the roof.

These HVAC units are not actually attached to the curb. They simply are sitting on the curb. — Brandon Reynolds, OEM Business Manager, Anchor Products

Anchor's own site says most rooftop units in service were set before anyone asked how they would hold in high wind, and that the question usually arrives with a code review or an insurance inspection. For the facility manager, years of trouble-free operation answer nothing. The thing to find out is whether anyone ever ran the calculation.

A hold-down bracket by itself is not a wind rating

MicroMetl wrote in January 2026 that a hold-down bracket added to a standard curb fulfils no wind code requirement on its own. A hold-down bracket screws into the base rails of the unit at one end and into the curb at the other, and a series of them keeps the unit from lifting off the curb, the company explained in its own material. What code looks for is the whole path: brackets sized for the unit, a curb sized for the brackets, and an anchorage from curb to structure, with screw types, quantities and metal gauge specified, all reviewed and stamped by a professional engineer registered in the project's state.

Here the vendor complicates Reynolds's thesis as much as it supports it. In many parts of the country, MicroMetl wrote, wind pressures are low enough that a unit's weight keeps it in place for its service life, and it is hurricane regions that need more than weight. That qualification leaves a facility manager to ask where this roof's design pressure falls, and Reynolds did not say where the building stands.

MicroMetl traced the modern curb rules to Hurricane Andrew in August 1992, which it said brought 165 mph winds and $25 billion to $26.5 billion in damage in Florida alone. Since then, the company wrote, the Florida Building Code's wind provisions have become the template across the United States.

Reynolds's answer is the position of this particular unit. It sits at the back gutter edge with a sidewalk and parked cars below.

The standard behind every one of those calculations is ASCE/SEI 7-22, Minimum Design Loads and Associated Criteria for Buildings and Other Structures. MIRO's May 2026 guide lays out which parts apply: Chapter 26 sets the design wind speed and exposure category for a site, Chapter 29 covers wind loads on rooftop structures and equipment, and the standard is adopted by reference in the 2021 International Building Code. ASCE's own contents for 7-22 list Chapter 30, Components and Cladding, alongside those, with errata to the standard effective February 2026.

So there is no single wind speed at which anchoring becomes mandatory. The threshold is a design pressure computed for each site and each piece of equipment, which is why the engineer's stamp matters more than the hardware.

Caulk is the only seal over the conduit fasteners

Along the back edge Reynolds found a run of small electrical conduit held by brackets screwed straight through the membrane, each screw head buried under caulk. A shutoff box nearby was fastened through the parapet membrane with no caulk at all. Water is getting into that wall whether the owner knows it or not, Reynolds said.

PHP Systems/Design, a rooftop support maker, wrote on its own site in April 2016 that every membrane penetration adds a weak link to the roof. Contractors seal each one, the company wrote, but most sealants dry out and crack over time and give moisture a path into the building, with mold and leaks the result. MIRO's May 2026 guide makes the parallel point about coverage: a penetration may affect the membrane warranty unless it is installed to the membrane manufacturer's approved details, meaning the maker's own drawings for how that penetration is flashed.

Carlisle SynTec now warrants its 90-mil EPDM membrane for 40 years, it announced in October 2024. The company said in a press release that the non-prorated material warranty on its Sure-Seal and Sure-White 90-mil sheets rests on accelerated weathering tests and on roofs past 40 years still in service, and that ballasted 60-mil systems built to 30-year detailing now qualify for 30-year warranties.

Reynolds did not name the membrane maker on this roof, and the owner's hope for two to three decades, as Reynolds relays it, sits well inside what the market now sells. The caulk over each screw head, by Reynolds's count, needs replacing roughly every year, or every other year at best. That gap is the story of this roof.

What an engineered attachment does that a caulked screw cannot

An engineered attachment moves the load off the sealant and onto a part designed to carry it. MIRO describes two non-penetrating mechanisms on its site. Ballasted bases counteract uplift with weight on a wide footprint, with the amount of weight calculated from the site's ASCE 7-22 design wind speed and the base geometry, while cable bracing and stanchions tether equipment laterally to the building perimeter or to structural members instead of fastening through the deck.

The company adds two cautions. A base that concentrates too much weight on too small a footprint depresses the insulation and creates a bowl where water pools, so the pounds per square inch on the membrane have to be checked against the roof's limit. And a support that shifts in wind will abrade the membrane under it.

Anchor's approach, described on its own site, flashes an anchor into the roof instead of resting on it. The U-Anchor base is a galvanized steel plate with rolled edges that sits under a cover membrane matched to the roofing brand, type and color, leaving a stainless stud at the surface for hardware to bolt to. For a unit already in place, the company's Existing Mechanical Tie Down runs cable from the unit to bases set around it and tensions the cable against uplift, so the unit and its curb stay where they are.

Anchor says each base is considered a component of the roof and is included in the roof warranty, and that the base model is chosen by the membrane on the building rather than by the equipment. That is the company's claim about its own product. Whether a given membrane maker accepts a given base is a question for that maker's detail drawings.

Set that next to what Reynolds found. A field-fabricated pocket is a small open-topped box built on the roof around a pipe or conduit and filled with sealant, and uncured EPDM flashing is rubber that has not been vulcanized, so it stretches around odd shapes but lacks the strength of the cured sheet. A bracket through the membrane with caulk on top has no plate spreading the load and no cover membrane over the hole.

FM Global measures uplift in pressure, and a pressure is not a wind speed

FM Global's test loads a roof assembly from below in 15 psf steps, each held for one minute. The Canadian Roofing Contractors Association (CRCA) summarized the method in a June 2007 bulletin: pressure rises in those increments until something fails, and the assembly earns a rating from FM 1-60 up to FM 1-999 matching the last pressure it survived. In a fully adhered system, any separation at all, including a field seam letting go, counts as failure.

A psf is a pound of pressure per square foot of roof. Because FM applies a safety factor of two, CRCA noted, an assembly rated 1-60 is recommended for a building whose design wind load is 30 psf, and the rating number has no relation to wind speed.

Those ratings describe the roof cover, insulation and deck, not the unit on the curb. They still frame the risk on an adhered rubber roof, because the same pressure difference that lifts a membrane is what Reynolds was describing when he rocked the unit.

CRCA also set out where FM's authority begins and ends. FM Approvals does its testing and certification in-house, and only an FM engineer can certify that a roof meets FM requirements, which applies when a project specifies them. The guidance sits in Property Loss Prevention Data Sheets 1-28, Design Wind Loads, and 1-29, Roof Deck Securement and Above-Deck Roof Components, which CRCA described as engineering guidelines.

That is the line between require and recommend. A code official enforces the adopted building code, while an insurer's data sheet is a condition of coverage and rating where the policy calls for it. Neither FM's guidance as CRCA summarizes it nor the ASCE standard publishes a count of how often unanchored units actually leave their curbs.

The conduit that pulls on its own flashing

The last stop on Reynolds's walk was a conduit that nothing held up. Its weight was dragging on the side wall of a field-fabricated pocket wrapped in uncured flashing, and the pocket was visibly leaning. On another unit, conduit rested on an old roof pipe and had bent downward between its first 90-degree turn and the next; when Reynolds lifted it, it floated free, which means its whole load had been sitting on the pipe flashing.

Neither the standards bodies nor the support manufacturers put a public price on lifting a conduit run onto proper supports or tying down a unit, and none of them prices the leak that follows a failed pocket. What a facility manager can compare is maintenance per penetration against the roof's remaining life. Every caulked screw head is a recurring line item, and a support that carries its own load is not.

Reynolds's walk suggests what a facility manager can do before winter without hiring anyone: put a hand on each rooftop unit, look under each conduit bracket for cracked caulk, find any fastener into a parapet with no seal over it, and ask whether a professional engineer ever stamped the attachment from unit to curb to structure. Anchor says the next segment in its blind inspection series will show the crew supporting and securing the equipment on this roof. The test Reynolds points to is the one he performed: a unit that moves under one hand is not attached.

Featured companies

Your experts belong here

Every story in MarketScale Building Management starts with a company putting its facilities engineers, energy managers, and service technicians on the record. Buyers are already reading this topic. The only question is whose experts they find.

Owners and facilities teams pick on trust, and your engineers turn that trust into inbound conversations.

Book DemoSee how it works15 minutes, straight to a calendar.

About the author

MarketScale Newsroom
MarketScale NewsroomEditorial Team, MarketScale

The MarketScale Newsroom reports on the companies, technologies, and trends shaping 16 B2B industries. It turns primary sources and expert commentary into clear, useful coverage for the people doing the work.

B2B Weekly

The week in Building Management, and sixteen other industries, every Monday.

Ten stories, one-line takes, five minutes. Free.

Building Management: are you visible to AI?

Before they reach out, Building Management buyers ask AI engines which vendors to trust. Explore how your experts, customers, and partners can become useful content for buyers and AI search.

Free Trial

You just read one Building Management expert. Your company is full of them.

This article was produced through MarketScale. The same platform turns your facilities engineers, energy managers, and service technicians into the articles, video, and social content Building Management buyers are searching for. Start a free trial and see it with your own people. For qualifying companies, no credit card, no demo required.

NPS +73 · 1,000+ creators · 38+ countries

What your free trial includes

Hands-on access to the MarketScale platform
Media requests to your crowd, remote recording, AI writing tools
No demo required. No credit card.
For qualifying companies. Company confirmation required.

More Building Management Insights

ASHRAE Guideline 43: a nine-step path to a hospital VMP

ASHRAE Guideline 43: a nine-step path to a hospital VMP

Guideline 43 asks hospitals to document how their HVAC actually runs, and a new Standard 170 addendum signals a shift toward risk-assessed operations.

  • 01Standard 170 sets what an operating room must be able to do; a Ventilation Management Program records who decided what it actually does after hours, and on what evidence.
  • 02The 2027 NFPA 99 recognizes HVAC Ventilation Management Programs in Chapter 9, and a September 2026 Standard 170 addendum requires a risk assessment before operating room ventilation is adjusted.
  • 03For hospitals whose inspectors still enforce older editions, the first useful step is confirming in writing which Standard 170 edition applies, since every later rule in the program depends on it.

Nov 17, 2026

Ken Sinclair's building autonomy roadmap starts with the sensor labels

Ken Sinclair's building autonomy roadmap starts with the sensor labels

Ken Sinclair's five-step roadmap for autonomous buildings keeps existing HVAC hardware and starts by tagging every sensor point in an open ontology. His checklist starts by mapping points into one semantic graph and ends with a one-subsystem pilot where a person approves setpoint changes.

  • 01Sinclair’s step one for autonomy is to map and tag existing automation points for usability. Siemens describes its AI-Assisted Data Onboarding as automating tagging and structuring for existing buildings.
  • 02Commissioning and fault-detection programs can achieve about 20% savings in some cases, according to a sponsored Facility Executive piece on campuses.

Nov 17, 2026

JLL survey: 75% say their FM procurement process lags

JLL survey: 75% say their FM procurement process lags

According to JLL, 87% of occupiers agree FM outsourcing will shift from labor-based to outcome-based pricing by 2030. In the same survey, 75% say procurement has not kept pace with their FM ambitions, and 71% split FM decisions on budget, delivery model and provider selection across two or three functions.

  • 01Nearly nine in ten occupiers expect to pay facilities providers for results by 2030, yet 71% still split the buying decision across two or three functions that each define success differently.
  • 02Strategic FM isn’t necessarily leaner: among JLL’s “strategic operators,” 64% plan bigger FM budgets and 58% plan more headcount even as AI and robotics scale.
  • 03A key question before drafting an outcome-based FM contract: who has the authority to align budget, delivery model and provider selection around one agreed scorecard and baseline?

Nov 16, 2026

Explore More Building Management Insights

Read more expert perspectives from across Building Management.

Browse Building Management Hub

About the Expert

MarketScale Newsroom
MarketScale Newsroom

Editorial Team

MarketScale

The MarketScale Newsroom reports on the companies, technologies, and trends shaping 16 B2B industries. It turns primary sources and expert commentary into clear, useful coverage for the people doing the work.

For B2B teams

Your experts could be publishing here

Stories like this one run on content MarketScale captures from real practitioners. See how your team's expertise becomes coverage in Building Management and beyond.

Book a Demo

Or call us. No forms required. We pick up. 214-945-2512